• P2113 Chemical Industry Pressure Gauge

    Tecsis GTS Pressure Gauges P2033 Chemical Industry Pressure Gauge

    Stainless Steel, Chemical Resistant, Glycerine Filled Pressure Gauge

    The Tecsis P2113 pressure gauge is ideal for the hard conditions and the high demands on pressure measurement in production facilities in chemical industry and other comparable branches the all stainless steel pressure gauges are the perfect fit. The stainless steel and other high-grade materials used for the measuring system and the casing mean that the P2113 is able to achieve resistance to aggressive media and environments.  

    To prevent wear based on pulsating pressures and mechanical vibrations, the housings are glycerine filled and thereby damped. The measuring system is of accuracy class 1.0, has overrange protection amounting to 1.3 times the max. rating and can be loaded up to the full scale value.

    The safety execution of the pressure gauges comprises a burstproof solid front between dial and Bourdon tube, a laminated safety glass as well as a blow-out back (according to EN 837-1/S3 ).

    Pressure gauges with glycerine filling are equipped with a compensation diaphragm. This diaphragm avoids a pressure rise in the case that is due to the temperature bound volume expansion of the liquid filling, thus avoiding indicated errors.

    Measuring Range:

    0... 0.6 bar to 0... 1000 bar

    Features
    Applications
    Mount & Casing

    • Connection position bottom, radial
    • With or without inductiv alarm-contact
    • Measuring system of high corrosion resistant materials, stainless steel or Monel 400
    • Resistant to chemicals
    • Accuracy class 1.0
    • Fulfills highest safety requirements to EN 837-1/S3
    • Solid front between measuring system and dial
    • Vibration-free display and long service life through glycerine or polybuten filling

    • Processing technology
    • Compressors
    • Machine & apparatus construction

     

     Model Case Bezel Window Dial Pointer Movement Connection
     P2113
    Stainless steel, 1.4301 with blow-out back,
    solid front Scale ranges ≤ 0 … 16 bar,
    with compensating valve to vent case
    stainless steel
    1.4301 bright
    bayonet ring
    Laminated
    safety
    glass
    aluminium, white, scale
    & black imprint
    aluminium,
    black
    Stainless
    Steel
    radial
    bottom


  • Sentech Refrigerant Monitors

    SenTech Corporation Refrigerant Monitors 'early warning' loss detection

    The Sentech refrigerant monitors are 'early warning' loss detection monitoring systems designed specifically for refrigerants. These environmental system IR-SNIF monitors are specialised refrigerant monitors that have been designed for applications such as comfort air, refrigeration and critical environment applications.

    The IR-SNIF models are cost effective, self contained active air-draw sampling systems offereing highly reliable infrared-based performance with the flexibility to satisfy a wide range of continuous monitoring applications.

    The monitors utilise NDIR [non-dispersive infrared] and pyroelectric [absorptive sensing] technology featuring multi-zone detection point capability from a single field-programmable self-contained metal enclosure featuring a unique built-in leak wait period that minimises nuisance false alarms.  

    Suitable applications for the Sentech Refrigeration Leak Monitors are:

    • Supermarkets
    • Refrigerated warehousing
    • Industrial process cooling
    • Sports arenas
    • Agricultural process and stroage 
    Comfort Air Applications Refrigerant Applicaitons Critical Environment Applicaitons
    • Office buildings
    • Hospitals
    • Schools & Universities
    • Factories
    • Government facilities
    • Supermarkets
    • Refrigerated warehousing
    • Industrial process cooling
    • Sports arenas
    • Agricultural process and stroage
    • Corporate data centres
    • Telecom switching factilities
    • Process control rooms
    • Industrial robotic systems
    • Medical diagnostic centres
    • Clean rooms

     

    SenTech IR SNIF 123 and 223 Refrigeration Gas Leak Monitors

    IR-SNIF 1,2,3

    IR-SNIF MCD

    Environmenatal systems single channel loss monitors Environmenatal systems multi channel loss monitors
    • Detects all Halogen based refrigerants
    • Refrigerant type can be field cahnged without recalibration
    • Continuous ditital display of system status
    • Analogue output for remote monitoring
    • System malfunction detection and indication
    • Visual alarm indication
    • Models are available to accommodate sampling points located up to 76 meters from the unit
    • Fresh air inlet for automatic rezeroing
    • Individually adjusted alarm point for each gas type being monitoried
    • Detects all Halogen based refrigerants
    • Refrigerant type can be field changed without calibration
    • Continuous digital display of system status
    • Analogue output for remote monitoring
    • System malfunction detection and indication
    • Visual alarm indication
    • Models are available to accommodate sampling points located up to 76 meters from the unit
    • Fresh air inlet for automatio rezeroing
    • Individually adjusted alarm point for each gas type being monitored

    Specifications

      IR-SNIF 1,2,3 IR-SNIF MCD
     Sensitivity as low as 10 PPM as low as 1 PPM
     Weight 7.2 kg 14.4 kg
     Power requirements 120/240 Volt 50/60 Hz 120/240 Volt 50/60 Hz
     Range 0 to 1000 PPM 0 to 1000 PPM
     Alarm trip points
     Low Alarm 0 to 100% full scale 0 to 100% full scale
     Main Alarm 0 to 100% full scale 0 to 100% full scale
     High Alarm 0 to 100% full scale 0 to 100% full scale
     Operating environment range 0°c to 50°c 0°c to 50°c
     Alarm Outputs
    Indicator Light
    Alarm Relays with 4 Form C contacts (2 amps max)
    Indicator Light
    3 Alarm Relays, 1 Horn Control Relay each with
    4 Form C contacts (amps max)